Report Suspicious Activity
Overview
Quick Details
Cooling Type:
Counter Flow
Material:
FRP
Place of Origin:
Delhi, India
Brand Name:
ABR cooling tower
Model Number:
ABR250

Specifications

Cooling towers are heat removal devices used to transfer process waste heat to the atmosphere.

TECHNICAL DATA

 

1. TOWER : Model No / Cap. ABR-250 (250TR [01 Cell)

a) Length 3350 mm (Approx).

b) Width 3350 mm (Approx)

c) Height 4375 mm (Approx)

d). Casing FRP (Fibre Reinforced Plastic)

e). Fills. PVC

f). Drift Eleminator. PVC

g). Operating weight. 6500 Kg.(Approx.) Eah

2. FAN:

a). No Of Unit 01

b). Type Axl flow (variable pitch)

c). Diameter. 1800mm

d). Hub / Blade HUB Aluminium Blade FR.P / Aluminium

3. MOTOR:

a). No Of unit. 01

b). Size H.P. 10 HP Cooling Tower Special Motor

c). RPM 720 RPM 415 + 10% 50 Cycles

d). Shaft. Extended shaft Flange mounted.

e). Type. Sq. Cage (IP 55 weather Proof) T.E.F.C.

4. Duty conditions:

a). Hot water inlet temp. 36 Deg C

b). Cold water outlet temp. 32 Deg C

c). Water flow rate. 2500 – 2700 LPM

d). WBT prevailing at site. 29 Deg

5. DRIFT LOSSES: 0.2%

6. EVAPORATION LOSSES: 0.025%

7. HARDWARE:

a). Nut, Bolts, & Washers. Electroplated.

8. LADDER: G.I.

9. DISTRIBUTION SYSTEM:

a). Type. Spray Nozzles..